Especificación

The FOGRod comes in three lengths – 7.5 ft, 5ft and 3ft – each type has 10 contacts (separated by 9″, 6″ and 3″ respectively). If you need a 10ft or 15ft Fogrod we supply 2x 5ft or 2x 7.5ft FOGRods (and 1 LIT). Each FOGRod has the option of two cable lengths – 50 ft or 100 ft and we manufacture custom units with longer cables to order. The FOGRod also comes with a 10-year warranty.

We also have 3-contact and single contact Fogrods, with a failsafe wire (for testing cable integrity). Contact us for more information.

If you don’t already have D.C. power in the panel (e.g. powering a PLC or telemetry unit) you will need a D.C. power supply.

Download the FOGRod Brochure

Kits

Part NumberDescription Part Numbers in Kit
Level-3-503 ft FOGRod with 50 ft of cable, cleaning bracket + LITFOG-3-50 | LIT-100
Level-5-505 ft FOGRod with 50 ft of cable, cleaning bracket + LITFOG-5-50 | LIT-100
Level-7.5-50 7.5 ft FOGRod with 50 ft of cable, cleaning bracket + LITFOG-7.5-50 | LIT-100
Level-3-1003 ft FOGRod with 100 ft of cable, cleaning bracket + LITFOG-3-100 | LIT-100
Level-5-1005 ft FOGRod with 100 ft of cable, cleaning bracket + LITFOG-5-100 | LIT-100
Level-7.5-1007.5 ft FOGRod with 100 ft of cable, cleaning bracket + LITFOG-7.5-100 | LIT-100
Level-10-50"10ft FOGRod" with 50 ft of cable, cleaning bracket + LITFOG-5-50 (qty 2) | LIT-100
Level-10-100 "10ft FOGRod" with 100 ft of cable, cleaning bracket + LITFOG-5-100 (qty 2) | LIT-100
Level-15-50"15ft FOGRod" with 50 ft of cable, cleaning bracket + LITFOG-7.5-50 (qty 2) | LIT-100
Level-15-100 "15ft FOGRod" with 100 ft of cable, cleaning bracket + LITFOG-7.5-100 (qty 2) | LIT-100

Options

PSU-12-NB12v DC power supply, no battery backup. Dimensions: 0.9" x 3.5" x 3.9" (WxHxD)
PSU-24-NB24v DC power supply, no battery backup. Dimensions: 0.9" x 3.5" x 3.9" (WxHxD)
FOG-ISBFor Intrinsic Safety (Class I, Division 1): 6x 2-channel IS barriers - Z967 by P&F (qty 6).
LIT-EW5Extend LIT-100 warranty to 5 years
FOG-CSSFOGRod Cable Splice Shield Kit - eliminate electrical noise when splicing cable

LIT Specifications

Environmental
Power supply10v-30v d.c., 4W
Temperature ratingOperating: -40 °F to 158 °F (-40 °C to +70 °C) | Storage: -40 °F to 185 °F (-40 °C to +85 °C)
Dimensions7" (W) x 4" (H) x 1.5" (D) (178mm x 102mm x 38mm)
Enclosure typeHigh impact ABS with DIN rail clip
ApprovalUL | C-UL (CSA) - see listing on UL website | CE approval (Europe) | RCM (Australia)
WarrantyTwo years, extendable to five years (order part number LIT-EW5)
 
I/O and Indication
Relay Outputs – Level10 relays, rated at 250VAC / 30VDC 6A (resistive load), configurable as normally open or normally closed (N/O or N/C)
Relay Outputs - Faults 2 relays, rated at 250VAC / 30VDC 6A (resistive load), configurable as normally open or normally closed (N/O or N/C) - 1 relay for cable open circuit or short circuit | - 1 relay for contact dry below wet or FOG (fats, oils, grease) buildup
LEDs – Level10 green LEDs
LEDs – Fault & Power1 green LED for power | 4 red LEDs for faults — Cable Open Circuit; Cable Short Circuit; Wiring or Contact Fault; Clean FOGRod
Analog Output – Level4-20mA output, 4mA = zero level, 5mA = 10%, 6mA = 20%, etc. to 14mA = 100% | Maximum load depends on supply voltage
Accuracy better than 1%
FOGRod I/O11 FOGRod I/O - 8 VAC, low frequency: 10 level, 1 cable integrity (plus cable shield)
TerminalsAll terminals standard screw type
Setting
ConductivityDefault conductivity threshold = 50kΩ, range from 3k – 300kΩ
DIP switches1. Level relays – Normally Open / Normally Closed
2. Fault relays - Normally Open / Normally Closed
3. Level relays and LEDs – 1 sec / 10 sec activation
4. Clean FOGRod alert - On/Off

FOGRod Specifications

ConstructionCustom PVC
Metal contactsAL6XN (super-austenitic steel for very high corrosion resistance)
DimensionsDiameter – 1⅜ in (35mm)
FOG-7.5 – Length 7' 4in (2235mm), Separation between contacts 9" (229mm)
FOG-5 – Length 5' 1" (1549mm), Separation between contacts 6" (152mm)
FOG-3 – Length 2' 10" (864mm), Separation between contacts 3" (76mm)
WeightFOG-5: 5.5 lbs (2.5kg), excluding cable | FOG-7.5: 7.7 lbs (3.5kg), excluding cable
Temperature ratingOperating: -40 °F to 158 °F (-40 °C to +70 °C) | Storage: -40 °F to 185 °F (-40 °C to +85 °C)
CableCustom 11-core cable with braided shield | PVC insulation & outer jacket | Conductor size 20 AWG or greater
Hazardous Locations ApprovalClass I Division 2 Group D (methane) directly connected to the LIT (no barrier) for USA & Canada - UL file E467390 - and see Division 2 Control drawing
Class I Division 1 connected to the LIT via an approved barrier - see the Division 1 status of the FOGRod and the Division 1 Control drawing
Warranty10 years
Mounting bracket Aluminum (powder coated) with tough polyurethane cleaning pad (anchors, S-hook and cable tie included)
*Specifications subject to change without notice.

10-Year Warranty on the FOGRod

What is it made of to have such a long life?

• Main body – Custom PVC plastic
• Metal contacts – AL6XN stainless steel

PVC is very resistant to corrosion and has been used for decades for municipal sewage.

The FOGRod comes in three lengths – 7.5 ft, 5ft and 3ft – each type has 10 contacts (separated by 9″, 6″ and 3″ respectively). If you need a 10ft or 15ft Fogrod we supply 2x 5ft or 2x 7.5ft FOGRods (and 1 LIT). Each FOGRod has the option of two cable lengths – 50 ft or 100 ft and we manufacture custom units with longer cables to order. The FOGRod also comes with a 10-year warranty.

We also have 3-contact and single contact Fogrods, with a failsafe wire (for testing cable integrity). Contact us for more information.

If you don’t already have D.C. power in the panel (e.g. powering a PLC or telemetry unit) you will need a D.C. power supply.

Download the FOGRod Brochure

Kits

Part NumberDescription Part Numbers in Kit
Level-3-503 ft FOGRod with 50 ft of cable, cleaning bracket + LITFOG-3-50 | LIT-100
Level-5-505 ft FOGRod with 50 ft of cable, cleaning bracket + LITFOG-5-50 | LIT-100
Level-7.5-50 7.5 ft FOGRod with 50 ft of cable, cleaning bracket + LITFOG-7.5-50 | LIT-100
Level-3-1003 ft FOGRod with 100 ft of cable, cleaning bracket + LITFOG-3-100 | LIT-100
Level-5-1005 ft FOGRod with 100 ft of cable, cleaning bracket + LITFOG-5-100 | LIT-100
Level-7.5-1007.5 ft FOGRod with 100 ft of cable, cleaning bracket + LITFOG-7.5-100 | LIT-100
Level-10-50"10ft FOGRod" with 50 ft of cable, cleaning bracket + LITFOG-5-50 (qty 2) | LIT-100
Level-10-100 "10ft FOGRod" with 100 ft of cable, cleaning bracket + LITFOG-5-100 (qty 2) | LIT-100
Level-15-50"15ft FOGRod" with 50 ft of cable, cleaning bracket + LITFOG-7.5-50 (qty 2) | LIT-100
Level-15-100 "15ft FOGRod" with 100 ft of cable, cleaning bracket + LITFOG-7.5-100 (qty 2) | LIT-100

Options

PSU-12-NB12v DC power supply, no battery backup. Dimensions: 0.9" x 3.5" x 3.9" (WxHxD)
PSU-24-NB24v DC power supply, no battery backup. Dimensions: 0.9" x 3.5" x 3.9" (WxHxD)
FOG-ISBFor Intrinsic Safety (Class I, Division 1): 6x 2-channel IS barriers - Z967 by P&F (qty 6).
LIT-EW5Extend LIT-100 warranty to 5 years
FOG-CSSFOGRod Cable Splice Shield Kit - eliminate electrical noise when splicing cable

LIT Specifications

Environmental
Power supply10v-30v d.c., 4W
Temperature ratingOperating: -40 °F to 158 °F (-40 °C to +70 °C) | Storage: -40 °F to 185 °F (-40 °C to +85 °C)
Dimensions7" (W) x 4" (H) x 1.5" (D) (178mm x 102mm x 38mm)
Enclosure typeHigh impact ABS with DIN rail clip
ApprovalUL | C-UL (CSA) - see listing on UL website | CE approval (Europe) | RCM (Australia)
WarrantyTwo years, extendable to five years (order part number LIT-EW5)
 
I/O and Indication
Relay Outputs – Level10 relays, rated at 250VAC / 30VDC 6A (resistive load), configurable as normally open or normally closed (N/O or N/C)
Relay Outputs - Faults 2 relays, rated at 250VAC / 30VDC 6A (resistive load), configurable as normally open or normally closed (N/O or N/C) - 1 relay for cable open circuit or short circuit | - 1 relay for contact dry below wet or FOG (fats, oils, grease) buildup
LEDs – Level10 green LEDs
LEDs – Fault & Power1 green LED for power | 4 red LEDs for faults — Cable Open Circuit; Cable Short Circuit; Wiring or Contact Fault; Clean FOGRod
Analog Output – Level4-20mA output, 4mA = zero level, 5mA = 10%, 6mA = 20%, etc. to 14mA = 100% | Maximum load depends on supply voltage
Accuracy better than 1%
FOGRod I/O11 FOGRod I/O - 8 VAC, low frequency: 10 level, 1 cable integrity (plus cable shield)
TerminalsAll terminals standard screw type
Setting
ConductivityDefault conductivity threshold = 50kΩ, range from 3k – 300kΩ
DIP switches1. Level relays – Normally Open / Normally Closed
2. Fault relays - Normally Open / Normally Closed
3. Level relays and LEDs – 1 sec / 10 sec activation
4. Clean FOGRod alert - On/Off

FOGRod Specifications

ConstructionCustom PVC
Metal contactsAL6XN (super-austenitic steel for very high corrosion resistance)
DimensionsDiameter – 1⅜ in (35mm)
FOG-7.5 – Length 7' 4in (2235mm), Separation between contacts 9" (229mm)
FOG-5 – Length 5' 1" (1549mm), Separation between contacts 6" (152mm)
FOG-3 – Length 2' 10" (864mm), Separation between contacts 3" (76mm)
WeightFOG-5: 5.5 lbs (2.5kg), excluding cable | FOG-7.5: 7.7 lbs (3.5kg), excluding cable
Temperature ratingOperating: -40 °F to 158 °F (-40 °C to +70 °C) | Storage: -40 °F to 185 °F (-40 °C to +85 °C)
CableCustom 11-core cable with braided shield | PVC insulation & outer jacket | Conductor size 20 AWG or greater
Hazardous Locations ApprovalClass I Division 2 Group D (methane) directly connected to the LIT (no barrier) for USA & Canada - UL file E467390 - and see Division 2 Control drawing
Class I Division 1 connected to the LIT via an approved barrier - see the Division 1 status of the FOGRod and the Division 1 Control drawing
Warranty10 years
Mounting bracket Aluminum (powder coated) with tough polyurethane cleaning pad (anchors, S-hook and cable tie included)
*Specifications subject to change without notice.

10-Year Warranty on the FOGRod

What is it made of to have such a long life?

• Main body – Custom PVC plastic
• Metal contacts – AL6XN stainless steel

PVC is very resistant to corrosion and has been used for decades for municipal sewage.

Aún estamos traduciendo esta página – si tienes alguna pregunta, por favor, envíanos un correo electrónico y te responderemos a la brevedad

The FOGRod comes in two lengths – 5 ft and 7.5 ft. And each FOGRod length has the option of two cable lengths – 50 ft and 100 ft. If you don’t already have D.C power in the panel (e.g. powering a PLC or telemetry supply) you will need a mains to D.C. power supply. The FOGRod also comes with a 10-year warranty.

Download the FOGRod Brochure

Kits

Part NumberDescriptionPart Numbers in Kit
Level-5-505 ft FOGRod with 50 ft of cable, cleaning bracket + LITFOG-5-50 | LIT-100
Level-7.5-507.5 ft FOGRod with 50 ft of cable, cleaning bracket + LITFOG-7.5-50 | LIT-100
Level-5-1005 ft FOGRod with 100 ft of cable, cleaning bracket + LITFOG-5-100 | LIT-100
Level-7.5-1007.5 ft FOGRod with 100 ft of cable, cleaning bracket + LITFOG-7.5-100 | LIT-100

Options

PSU-12-NBMains to 12v power supply, no battery backup
PSU-24-NBMains to 24v power supply, no battery backup

LIT Specifications

Environmental
Power supply10v-30v d.c., 4W
Temperature ratingOperating: -40 °F to 158 °F (-40 °C to +70 °C) | Storage: -40 °F to 185 °F (-40 °C to +85 °C)
Dimensions7" (W) x 4" (H) x 1.5" (D) (178mm x 102mm x 38mm)
Enclosure typeHigh impact ABS with DIN rail clip
ApprovalUL | C-UL (CSA) - see listing on UL website | CE approval (Europe) | RCM (Australia)
WarrantyTwo years, extendable to five years (order part number LIT-EW5)
 
I/O and Indication
Relay Outputs – Level10 relays, rated at 250VAC / 30VDC 6A (resistive load), configurable as normally open or normally closed (N/O or N/C)
Relay Outputs - Faults 2 relays, rated at 250VAC / 30VDC 6A (resistive load), configurable as normally open or normally closed (N/O or N/C) - 1 relay for cable open circuit or short circuit | - 1 relay for contact dry below wet or FOG (fats, oils, grease) buildup
LEDs – Level10 green LEDs
LEDs – Fault & Power1 green LED for power | 4 red LEDs for faults — Cable Open Circuit; Cable Short Circuit; Wiring or Contact Fault; Clean FOGRod
Analog Output – Level4-20mA output, 4mA = zero level, 5mA = 10%, 6mA = 20%, etc. to 14mA = 100% | Maximum load depends on supply voltage
Accuracy better than 1%
FOGRod I/O11 FOGRod I/O - 8 VAC, low frequency: 10 level, 1 cable integrity (plus cable shield)
TerminalsAll terminals standard screw type
Setting
ConductivityDefault conductivity threshold = 50kΩ, range from 3k – 300kΩ
DIP switches1. Level relays – Normally Open / Normally Closed
2. Fault relays - Normally Open / Normally Closed
3. Level relays and LEDs – 1 sec / 10 sec activation
4. Clean FOGRod alert - On/Off

FOGRod Specifications

ConstructionCustom PVC
Metal contactsAL6XN (super-austenitic steel for very high corrosion resistance)
DimensionsDiameter – 1⅜ in (35mm)
FOG-7.5 – Length 7' 4in (2235mm), Separation between contacts 9" (229mm)
FOG-5 – Length 5' 1" (1549mm), Separation between contacts 6" (152mm)
FOG-3 – Length 2' 10" (864mm), Separation between contacts 3" (76mm)
WeightFOG-5: 5.5 lbs (2.5kg), excluding cable | FOG-7.5: 7.7 lbs (3.5kg), excluding cable
Temperature ratingOperating: -40 °F to 158 °F (-40 °C to +70 °C) | Storage: -40 °F to 185 °F (-40 °C to +85 °C)
CableCustom 11-core cable with braided shield | PVC insulation & outer jacket | Conductor size 20 AWG or greater
Hazardous Locations ApprovalClass I Division 2 Group D (methane) directly connected to the LIT (no barrier) for USA & Canada - UL file E467390 - and see Division 2 Control drawing
Class I Division 1 connected to the LIT via an approved barrier - see the Division 1 status of the FOGRod and the Division 1 Control drawing
Warranty10 years
Mounting bracket Aluminum (powder coated) with tough polyurethane cleaning pad (anchors, S-hook and cable tie included)
*Specifications subject to change without notice.

10-Year Warranty on the FOGRod

What is it made of to have such a long life?

• Main body – CPVC plastic
• Metal contacts – AL6XN stainless steel

PVC is very resistant to corrosion and has been used for decades for municipal sewage. CPVC has the same corrosion resistance as PVC but is stronger and even more resistant to cracking.

Aún estamos traduciendo esta página – si tienes alguna pregunta, por favor, envíanos un correo electrónico y te responderemos a la brevedad

The FOGRod comes in two lengths – 5 ft and 7.5 ft. And each FOGRod length has the option of two cable lengths – 50 ft and 100 ft. If you don’t already have D.C power in the panel (e.g. powering a PLC or telemetry supply) you will need a mains to D.C. power supply. The FOGRod also comes with a 10-year warranty.

Download the FOGRod Brochure

Kits

Part NumberDescriptionPart Numbers in Kit
Level-5-505 ft FOGRod with 50 ft of cable, cleaning bracket + LITFOG-5-50 | LIT-100
Level-7.5-507.5 ft FOGRod with 50 ft of cable, cleaning bracket + LITFOG-7.5-50 | LIT-100
Level-5-1005 ft FOGRod with 100 ft of cable, cleaning bracket + LITFOG-5-100 | LIT-100
Level-7.5-1007.5 ft FOGRod with 100 ft of cable, cleaning bracket + LITFOG-7.5-100 | LIT-100

Options

PSU-12-NBMains to 12v power supply, no battery backup
PSU-24-NBMains to 24v power supply, no battery backup

LIT Specifications

Environmental
Power supply10v-30v d.c., 4W
Temperature ratingOperating: -40 °F to 158 °F (-40 °C to +70 °C) | Storage: -40 °F to 185 °F (-40 °C to +85 °C)
Dimensions7" (W) x 4" (H) x 1.5" (D) (178mm x 102mm x 38mm)
Enclosure typeHigh impact ABS with DIN rail clip
ApprovalUL | C-UL (CSA) - see listing on UL website | CE approval (Europe) | RCM (Australia)
WarrantyTwo years, extendable to five years (order part number LIT-EW5)
 
I/O and Indication
Relay Outputs – Level10 relays, rated at 250VAC / 30VDC 6A (resistive load), configurable as normally open or normally closed (N/O or N/C)
Relay Outputs - Faults 2 relays, rated at 250VAC / 30VDC 6A (resistive load), configurable as normally open or normally closed (N/O or N/C) - 1 relay for cable open circuit or short circuit | - 1 relay for contact dry below wet or FOG (fats, oils, grease) buildup
LEDs – Level10 green LEDs
LEDs – Fault & Power1 green LED for power | 4 red LEDs for faults — Cable Open Circuit; Cable Short Circuit; Wiring or Contact Fault; Clean FOGRod
Analog Output – Level4-20mA output, 4mA = zero level, 5mA = 10%, 6mA = 20%, etc. to 14mA = 100% | Maximum load depends on supply voltage
Accuracy better than 1%
FOGRod I/O11 FOGRod I/O - 8 VAC, low frequency: 10 level, 1 cable integrity (plus cable shield)
TerminalsAll terminals standard screw type
Setting
ConductivityDefault conductivity threshold = 50kΩ, range from 3k – 300kΩ
DIP switches1. Level relays – Normally Open / Normally Closed
2. Fault relays - Normally Open / Normally Closed
3. Level relays and LEDs – 1 sec / 10 sec activation
4. Clean FOGRod alert - On/Off

FOGRod Specifications

ConstructionCustom PVC
Metal contactsAL6XN (super-austenitic steel for very high corrosion resistance)
DimensionsDiameter – 1⅜ in (35mm)
FOG-7.5 – Length 7' 4in (2235mm), Separation between contacts 9" (229mm)
FOG-5 – Length 5' 1" (1549mm), Separation between contacts 6" (152mm)
FOG-3 – Length 2' 10" (864mm), Separation between contacts 3" (76mm)
WeightFOG-5: 5.5 lbs (2.5kg), excluding cable | FOG-7.5: 7.7 lbs (3.5kg), excluding cable
Temperature ratingOperating: -40 °F to 158 °F (-40 °C to +70 °C) | Storage: -40 °F to 185 °F (-40 °C to +85 °C)
CableCustom 11-core cable with braided shield | PVC insulation & outer jacket | Conductor size 20 AWG or greater
Hazardous Locations ApprovalClass I Division 2 Group D (methane) directly connected to the LIT (no barrier) for USA & Canada - UL file E467390 - and see Division 2 Control drawing
Class I Division 1 connected to the LIT via an approved barrier - see the Division 1 status of the FOGRod and the Division 1 Control drawing
Warranty10 years
Mounting bracket Aluminum (powder coated) with tough polyurethane cleaning pad (anchors, S-hook and cable tie included)
*Specifications subject to change without notice.

10-Year Warranty on the FOGRod

What is it made of to have such a long life?

• Main body – CPVC plastic
• Metal contacts – AL6XN stainless steel

PVC is very resistant to corrosion and has been used for decades for municipal sewage. CPVC has the same corrosion resistance as PVC but is stronger and even more resistant to cracking.